How to Calculate the Maximum Enclosure Size for an Ex pz Purge and Pressurization System

Posted by Brent Dean on Fri, Sep 09, 2016

The maximum size of an Ex pz purge enclosure is determined by the pressure and flow that can be reached inside the enclosure. For this 'how to' post, I'll use our 5500 series purge system for the examples.

Depending on your application, there are three vent options that you can use with your system. The EPV-5500-…-01, EPV-5500-…-02, or EPV-5500-…-03. Each vent opens at a different back pressure and has different flow rates, which are listed below.

Read More

Topics: Purge/ Pressurization Systems

What Are the Differences Between the 3 Vents for the 5500 Type Z Purge and Pressurization System?

Posted by Brent Dean on Fri, Jun 17, 2016

When using the 5500 Type Z purge and pressurization system, you are given 3 vent options to choose from.  This gives you the option to choose a vent based on the needs of your application. The 3 models are:

Read More

Topics: Purge/ Pressurization Systems

How to Calculate Purge Time with the 5500 Type Z Purge and Pressurization System

Posted by Brent Dean on Fri, Apr 29, 2016

To calculate the purging time on our 5500 series Type Z purge system, there are four variables that you need to know:

Read More

Topics: Purge/ Pressurization Systems

Class I Applications for Type Y and Type Z Purge Systems

Posted by Brent Dean on Fri, Mar 01, 2013

Differences between the WPS and WPSA pressure switches

When selecting a Type Y or Type Z purge system, how do you know when to select the WPS (EPSK-1) or WPSA (EPSK-1A) pressure switch, and what is the difference? When selecting which pressure switch to use, first you must determine what hazardous gas group your enclosure is going to be located in (Group A, B, C, D, etc.).

The WPS pressure switch is rated for Class I Division 1 or 2 gas groups C and D. The WPSA switch is rated for Class I Division 1 or 2 gas groups A-D. For gas group C or D, you can use either switch. However, for gas group A or B, you must use the WPSA switch because it is certified for this area.

Read More

Topics: Purge/ Pressurization Systems, Ask an Expert, Approvals/ Certifications

How to Configure the ID Address on an Industrial Barcode Reader

Posted by Brent Dean on Tue, Dec 11, 2012

Configuring the Wireless PSCAN-M and Base Station PSCAN-B

Configuring an industrial barcode reader doesn’t have to be complicated. The following steps will help you to configure our PSCAN-M barcode readers.

Read More

Topics: Troubleshooting, Industrial Monitors/ HMI

Calculating Purge Times on Purge and Pressurization Systems in a Few Easy Steps

Posted by Brent Dean on Tue, Jul 17, 2012

Calculations for Type X, Type Y, Type Z, or Ex pz purge systems

Read More

Topics: Troubleshooting, Purge/ Pressurization Systems, Ask an Expert